Model |
TF30KW-IGBT |
Rated Power |
30KW |
Nominal battery voltage |
192V/240V/360V |
Input |
DC input range |
168-240VDC (192V) / 210-300VDC(240V) / 315-450VDC(360V) |
AC Mains input range |
140-275VAC (110/120/220/230/240VAC) ±4% |
AC input frequency |
50Hz: 45-65Hz / 60Hz: 55-65Hz±0.5Hz (50Hz/60Hz automatic recognition) |
Protection |
Low battery alarm |
≤168VDC (192V) / ≤210VDC(240V) / ≤ 315VD(360V) alarm |
Low battery protection |
≤160VDC (192V) / ≤200VDC(240V) / ≤300VDC(360V) automatic shutdown |
High battery alarm |
≥240VDC(192V) / ≥300VDC(240V) / ≥450VDC(360V) alarm |
High battery protection |
≥272VDC(192V) / ≥340VDC(240V) / ≥510VDC(360V) automatic shutdown |
Over load protection |
110%<loading<150%, shutdown after 60s alarm, loading>150%, shutdown after 20s alarm |
High temperature |
Built-in temperature real time sensor, ≥85℃ alarm, ≥90℃ automatic shutdown |
Short circuit protection |
Automatic shutdown |
Output |
Transfer efficiency |
≥92% |
Output frequency |
(DC battery mode) 60/50Hz±1% |
Output wave form |
Pure sine wave |
Output voltage |
(AC mains mode) stable 110/120/220/230/240VAC ±10% output (built-in AVR stablizer) |
AVR output stablizer |
AC mains<170VAC±5% swtich to DC battery mode, AC mains>180VAC ±5% return to AC mains mode; |
AC mains>275VAC ±5% swtich to DC battery mode, AC mains<255VAC ±5% return to AC |
Output frequency |
(AC mains mode) automatic tracing from AC input |
Other |
Transfer time |
Bult- in AC bypass replay (≤4ms) |
Display |
LCD Display with function buttons |
Cooling system |
Intelligent cooling fan control system |
≤42℃ slow fan, ≥45℃ fast fan |
AC Charger |
7 battery types mode |
Gel U.S.A. / Gel European / A.G.M.1 / A.G.M.2 / Sealed lead acid / Open lead acid / Calcium(open) /Deep sulphation cycle 15.5 for 4 hrs |
AC charging Voltage |
217.6-227.2VDC(192V)/272-284VDC(240V)/408-426VDC(360V) |
AC charging current |
0-35A: 5A / 10A / 20A / 25A / 30A / 35A, 6 stages charging current adjustable |
3 Stages charging |
Boost charging, direct charging, float charging |
AC over charge protection |
Battery voltage ≧256VDC(192V) ≧320VDC(240V) ≧ 480VDC(360V), stop charging after 60s alarm |
Working mode (Optional) |
1 |
AC mains priority |
Always use AC mains as priority input to provide AC output and automatically charge the battery, only |
stops charging when battery is fully charged, and only starts DC to AC converting untill AC mains is off |
DC battery priority |
2 |
Always use DC battery as priority input to provide AC output, for 12V system, when battery≥13V, starts |
DC to AC converting; when battery≤10.5V during converting, switch to AC mains mode to provide AC output and automatically start charging the battery (for 24V/48V system, multiply by 2/4 accordingly) |
Environment |
Temperature |
-20~+75℃ |
Humidity |
<95% |
Appearance |
Product size (mm) |
750*370*845 mm |
785*580*1197 mm |
Packing size (mm) |
850*600*1370mm |
950*730*1440 mm |
Net Weight (kg) |
250kg |
290kg |
Gross Weight (kg) |
265kg |
305kg |
*Product specifications are subject to change without further notice |